| Model |
48-60/2000 HE |
| Part number |
241115.705 |
| INPUT DATA |
| Voltage (nominal) |
185 - 275 VAC / 185 - 275 VDC |
| Voltage (operating range) |
85 - 300 VAC / 80 - 300 VDC |
| Current (maximum) @ nominal input, full load |
11.6 ARMS |
| Frequency |
45 - 66 Hz / 0 Hz |
| Power Factor |
> 0.99 at 50% load or more |
| THD |
< 5% at 100% load |
| Protection |
Fuse in L & N, Varistor, Shutdown when input voltage is out of operating range |
| OUTPUT DATA |
| Voltage (default) 1) |
53.5 VDC (67 VDC in 60V mode) |
| Voltage (adjustable range) 1) |
39.9 - 72 VDC |
| Power (maximum) @ nominal input |
2000 W (@VOUT ≥ 48VDC) |
| Power @ 85 VAC |
750 W |
| Current (maximum) @ nominal input |
41.6 A (@VOUT < 48VDC) |
| Hold up time, 1500W output power |
>20ms; output voltage > 53.5 VDC (60V mode) |
| Current sharing (10 - 100% load) |
±5% of maximum current from 10 to 100% load |
| Static Voltage regulation (10 - 100% load) |
±0.5% |
| Dynamic Voltage regulation |
±5.0% for 10-80% or 80-10% load variation, regulation time < 50ms |
| Ripple & noise |
< 150 mVPP , 30 MHz bandwidth / < 2 mVRMS psophometric |
| Protection |
Fuse , Short circuit proof, High temperature protection, Over voltage Shutdown |
| OTHER SPECIFICATIONS |
| Efficiency |
96.2 % |
| Isolation |
3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth |
|
Alarms: Red LED
|
Low / high input voltage shutdown, High / low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low output voltage alarm,
CAN bus failure
|
| Warnings: Yellow LED |
Rectifier in power de-rate mode, Remote output current limit activated, Input voltage out of range, flashing at overvoltage, Loss of CAN communication with controller |
| Normal operation: Green LED |
| MTBF (Telcordia SR-332 Iss.I method III (a)) |
>350 000 (@ Tambient : 25 °C) |
| Operating temp. (5-95% RH n.cond. hum.) |
-40 to + 75°C [-40 to +167°F] |
| Max output power de-rates above temp / to |
45°C [113°F] / 1200W @ 75°C[167°F] |
| Storage temperature |
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
| Dimensions[WxHxD] / Weight |
109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.950 kg (4.3lbs) |
| DESIGN STANDARDS |
|
Electrical safety
|
EN 62368-1:2020+A11:2020, IEC 62368-1:2018, IEC 60950-1:2005+A2:2013 UL 62368-1:2019 , CSA C22.2 No.62368-1:2019 |
| EMC |
EN IEC 61000-6-1:2019, -6-2:2019, -6-4:2019, IEC 61000-6-5: 2015
EN 61000-6-3:2007 + A1:2011/AC:2012, ETSI EN 300 386:2020
|
|
Environment
|
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)
EU 2015/863 (RoHS), 2012/19/EU (WEEE), IEC 63000:2018, EN IEC 62474:2019
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
|